Commissioning Prosonic S FMU90 PROFIBUS DP
72 Endress+Hauser
Default configuration of the cyclic data telegram (1-channel version)
Valid for FMU90 - *****1***
"Level" operating mode
• AI 1
• Bytes 0 - 3: Level 1 (IEEE754); unit: m
• Byte 4: Status level 1
• AI 2
• Bytes 5 - 8: Distance 1 (IEEE754); unit: m
• Byte 9: Status distance 1
• AI 3
• Bytes 10 - 13: Temperature 1 (IEEE754); unit: °C
• Byte 14: Status temperature 1
"Flow" operating mode
• AI 1
• Bytes 0 - 3: Flow 1 (IEEE754); unit: m
• Byte 4: Status flow 1
• AI 2
• Bytes 5 - 8: Distance 1 (IEEE754); unit: m
• Byte 9: Status distance 1
• AI 3
• Bytes 10 - 13: Temperature 1 (IEEE754); unit: °C
• Byte 14: Status temperature 1
• AI 5
• Bytes 15 - 18: Value totalizer 1 (IEEE754)
• Byte 19: Status totalizer 1
• AI 6
• Bytes 20 - 23: Overflow totalizer 1 (IEEE754)
• Byte 24: Status totalizer 1
• AI 7
• Bytes 25 - 28: Value daily counter 1 (IEEE754)
• Byte 29: Status daily counter 1
• AI 8
• Bytes 30 - 33: Overflow daily counter 1 (IEEE754)
• Byte 34: Status daily counter 1
"Level+Flow" operating mode
• AI 1
• Bytes 0 - 3: Flow 1 (IEEE754); unit: m
• Byte 4: Status flow 1
• AI 2
• Bytes 5 - 8: Level 1 (IEEE754); unit: m
• Byte 9: Status distance 1
• AI 3
• Bytes 10 - 13: Distance 1 (IEEE754); unit: °C
• Byte 14: Status distance 1
• AI 4
• Bytes 15 - 18: Temperature 1 (IEEE754)
• Byte 19: Status temperature 1
• AI 5
• Bytes 20 - 23: Value totalizer 1 (IEEE754)
• Byte 24: Status totalizer 1