System integration Prosonic S FMU90 PROFIBUS DP
50 Endress+Hauser
Software addressing
Software addressing takes effect when DIP switch 8 on the PROFIBUS DP terminal area
is set to "SW (on)" (factory setting).
The address can then be configured via an operating tool (e.g. "DeviceCare" or
"FieldCare").
The configured address is displayed in the parameter Output/calculation → PROFIBUS
DP → Instrument address.
Hardware addressing
Address
Term.
DP
off
on
off
on
SW
HW
1
2
3
4
5
6
7
8
1
2
3
4
A(N)
66
B(P)
65
Address
off
on
SW
HW
1
2
3
4
5
6
7
8
A0038436
Hardware addressing takes effect when DIP switch 8 is set to "HW (off)". When set to "on",
the position of DIP switches 1 to 7 define the following values in the address:
Switch 1: value = 1
Switch 2: value = 2
Switch 3: value = 4
Switch 4: value = 8
Switch 5: value = 16
Switch 6: value = 32
Switch 7: value = 64