Commissioning Prosonic S FMU90 PROFIBUS DP
56 Endress+Hauser
9.3.5 Parameter set "Empty calibration"
E
Dh
1
A0035535
 46 Empty calibration for flume
1 Ultrasonic sensor
D Measured distance
h Upstream level
E Empty calibration: "Empty E"
E
h
D
1
A0035536
 47 Empty calibration for weirs
1 Ultrasonic sensor
D Measured distance
h Upstream level
E Empty calibration: "Empty E"
Navigation
Basic setup → Empty calibration
Parameters
Empty E
For flumes: specify the distance between the sensor membrane and the flume floor at
the narrowest point.
For weirs: specify the distance between the sensor membrane and the lowest point of
the weir crest.
Blocking distance
Indicates the blocking distance BD of the sensor.
9.3.6 Parameter set "Flow N"
Navigation
Basic setup → Flow N