The process display records an analogue measured value. This
value can be monitored using a max. 2 alarm set points.
A clear readable two colour LED display shows the value in
digital and bargraph from. Set point infringements are
permanently displayed. The analogue output retransmits the
displayed value as either a current or voltage signal.
Transmitters connected can be directly supplied with power
from the unit.
2. Mechanical installation
Installation hints:
- The installation area must be vibration free.
- The permissible operating ambient temperature
is -10 to +50°C.
- Protect the unit from heat sources.
Panel installation:
Prepare a panel cut out of 45
+0.6
x92
+0.8
mm (to DIN 43700).
Installation depth of the unit is 150 mm.
À Push the unit through the gasket and the front of the
panel cutout.
Á Hold the unit horizontally and fix the jackscrews to their
respective slots (top and bottom).
 Tighten the jackscrews evenly using a screwdriver.
92 mm
+0,8
45 mm
+0,6
96 mm
48 mm
LIMIT 1
LIMIT 2
Process display
43