The display
shows: “——-”
Fault signal analysis -
When using a 4-20 mA input
range the input signal from the
sensor is outside the specified
range (> 3.6 to < 3.85 mA or
> 20.4 to < 21.0 mA)
E 213 Please check the sensor
connected to the input for
correct operation.
The 7 segment
display shows a
measured
value, all Bar
graph LEDs are
off, the left LED
flashes.
The displayed measured
value is > 10 % under the 0%
value of the analogue output.
E 240 Check if a valid input signal is
connected, or set a smaller
value to the 0% analogue
output value (
BG LO, BG HI).
The 7 segment
display shows a
measured
value, all Bar
graph LEDs are
off, the right
LED flashes.
The displayed measured
value is > 10% over the 100%
value of the analogue output.
E 241 Check if a valid input signal is
connected, or set a larger
value to the 100% analogue
output value (
BG LO, BG HI).
The display
shows: “
E 290”
Setting of the comma position
is not possible, as minimum
one digital value cannot be
displayed.
E 290 Acknowledge using the “E”
push button (Fault message
is deleted). Check all values
with this comma position and
reduce if required.