Operation of the switch time delay DELY:
Using this setting a time delay
DELY between switch threshold
SETP and activating the alarm indicator/relay can be installed.
If the measurement value falls below the preset switch
threshold
SETP (without hysteresis) within the time delay DELY
then the switch delay time counter is reset to zero. The time
counter restarts after a new infringement of the preset switch
threshold
SETP.
This is also valid for minimum monitoring.
5.5 Operating parameters
Parameter Setting up selections
Default
settings
Actual
User code
CODE
User operation code.
An already set code can only
be changed if the old code is
first entered and the unit
setting up released. Then a
new code can be set.
Value:
0000to9999
There is no operation
code active if “0" is set
0
* Set point code
LICOD
Set point change requires
a release code entry
YES Set points are code
protected
NO Set points can be
changed without setting a
code
YES
This address is only active when an operation code is set up.
PARAM
À Relay de-energised
Measurement value
DELY
HYST
SETP
Process display
60