Example:
Input/Output:
- Input thermocouple Type S
- Internal temperature compensation
- 1100°C equals 4 mA
- 1300°C equals 20 mA
- Fault condition equals 3.6 mA at the analogue output
Set point 1:
- Minimum safety
- Switch point 1150 (°C)
- Hysteresis 10 (°C)
Set point 2:
- Minimum safety
- Switch point 1100 (°C)
- Hysteresis 50 (°C)
Setting up:
Menu group Address Value
Analogue input
INPUT Input range RANG
Curve CURVE
Comparison temperature COMPT
TYPE5
°C
INT
Display
DISPL Scale bargraph/analog. 0% BG LO
Scale bargraph/analog. 100% BG HI
1100,0
1300,0
Analogue output
OUTPT Output range RANG
Fault operation FAIL
4-20
MIN
Set point/fault monitor
LIM1 Mode MODE1
Set point SETP1
Hysteresis HYST1
MIN
1150,0
10,0
Set point/fault monitor
LIM2 Mode MODE2
Set point SETP2
Hysteresis HYST2
MIN
1100,0
50,0