Endress+Hauser RMA 422 - 8. Technical Data; Application and System Construction Specifications

Endress+Hauser RMA 422
150 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Green
LED
Red
LED
Effect Cause Fault
code
Solution
On Flash The 7
segment
display
shows a text
The unit is in analogue output or alarm
set point relay simulation mode.
E 200 End simulation mode.
Display
shows:
E 201
Both analogue inputs are switched off. E 201 Activate at least one
analogue input.
A measured
value or
NNNNN”is
shown in the
display
Cable open circuit monitor active -
Connection to the sensor is interrupted
on a connection of 4...20 mA, this means
the current is under
3.60 mA.
E 210
E 220
Please check the
connection of the
sensor at analogue
input 1
Please check the
connection of the
sensor at analogue
input 2.
Below range -
The measured signal connected to the
analogue input is >10% below the valid
measurement range. Is not valid for the
4...20 mA input range.
E 210
E 220
Please check the
connection of the
sensor at analogue
input 1.
Please check the
connection of the
sensor at analogue
input 2
The display
shows a
meas. value
or
UUUUU
Over range -
The measured signal connected to the
analogue input is >10% over the valid
measurement range. Is not valid for the
4...20 mA input range.
E 212
E 222
Please check the
connection of the
sensor at analogue
input 1.
Please check the
connection of the
sensor at analogue
input 2.
A meas.
Value or
-----”is
shown in the
display
Faulty signal monitoring -
On a 4...20 mA input range the signal
connected to the input is outside the
specified range ( >3.60 ...
<3.85 mA or >20.4 ... <21.0 mA)
E 213
E 223
Please check the
function of the sensor
connected to input 1.
Please check the
function of the sensor
connected to input 2.
The 7
segment
display
shows a
meas. value
The measured value calculated from the
two input signals lies below -19999 or
above 99999.
E 230 Check if the input
signals are valid, or
check the scaling of
the two analogue
inputs.
The 7
segment
display
shows a
meas. value
The measured value allocated to the
analogue output is below the -10% value
of the analogue output.
E 240
E 250
Please check if the
input signals are valid
or whether the
calculated values are
within a valid range,
or allocate a smaller
value to the 0% value
of the
analogue output 1 ,
analogue output 2.
Process transmitter
67