Control Options
You must enter an Installer Password to access the CONTROL menu from the Main Menu. The
following settings can be changed:
DEFAULT OPTION
CHANGE
HYSTERESIS
2°F (1°C)
0-6°F
(0-3°C)
Defines the number of degrees the temperature must go beyond a
setpoint prior to changing from HEAT to COOL mode or vice versa in
AUTO mode.
ANTICIPATION TIME 60 MIN 0 – 180 MIN
The time limit the thermostat is allowed to engage the equipment to
reach a desired temperature. The algorithm determines the time
required to reach the temperature, and engages the equipment prior to
the next Scheduled Setpoint in order to reach the desired temperature
at the appropriate time. The temperature may not be reached if the
ANTICIPATION TIME is less than the time required to heat (or cool) to
the desired temperature.
MAX RECOVERY
TIME
90 MIN 0 – 180 MIN
The maximum time the thermostat allows the equipment to reach a
desired temperature in 1
ST
stage heating (or cooling). If the thermostat
determines that the desired temperature will not be reached, it will
engage the second (or further) stage of heating (or cooling).