Control Options
You must enter an Installer Password to access the CONTROL menu from the Main Menu. The
following settings can be changed:
DEFAULT
OPTION
CHANGE
HYSTERESIS
2°F (1°C)
0-6°F
(0-3°C)
Defines the number of degrees the temperature must go beyond a
setpoint prior to changing from HEAT to COOL mode or vice versa in
AUTO mode.
ANTICIPATION TIME
60 MIN
0 180 MIN
The time limit before the Scheduled Setpoint that the thermostat is
allowed to start the equipment to reach a desired temperature. The
algorithm determines the time required to reach the temperature, and
engages the equipment prior to the next Scheduled Setpoint in order to
reach the desired temperature at the appropriate time. The
temperature may not be reached if the ANTICIPATION TIME is less
than the time required to heat (or cool) to the desired temperature.
MAX RECOVERY
TIME
90 MIN
0 180 MIN
The maximum time the thermostat allows the equipment to heat or cool
to a desired temperature in 1
ST
stage heating (or cooling). If the
thermostat determines that the desired temperature will not be
reached, it will engage the second (or further) stage of heating (or
cooling).