EasyManua.ls Logo

Enertech XT024 - Condensation Drain Connection

Enertech XT024
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
Enertech Global IOM, XT Models
Condensation Drain Connection
Connect the EZ-Trap to the equipment condensate
drain connection as shown in gures 9a through 9d.
The condensate line must be trapped a minimum
of 1.0” as shown on diagram. The condensate line
should be pitched away from the unit a minimum
of 1/4” per foot. The condensate line from the unit
drain connection to the P-trap should be sloped
downward. For moreinformation on installing EZ-Trap,
see installationsheet that comes with the EZ-Trap Kit.
Always install the air vent after the trap.
Note: Connect the drain through the trap to the
condensation drain system in conformance
to local plumbing codes.
Part Number Description
ACDT1A EZ-Trap ¾” Kit
ACDT2A EZ-Trap 1” Kit
Figure 9a: Condensation Drain Connection
Figure 9d: Right Overow Sensor Connection
Figure 9c: Left Overow Sensor Connection
Note: Make Sure the condensate overow sensor is
mounted to the side closest to the drain being used
as shown in gures 9c and 9d below.
Section 5: Unit Piping Installation
Figure 9b: Condensation Drain Drop

Table of Contents

Related product manuals