19
IOM, XT Models Enertech Global
Flush Cart Design
The Enertech Manufacturing ush cart has been
designed to effectively and efciently ush the
earth loop and to facilitate injecting and mixing of
the antifreeze. The single most important element
in ow center reliability is the ability to remove all
the air and debris from the loop and to provide the
proper working pressure.
Features of the ush cart
Cylinder: HDPE, SDR15.5, 10” dia. (10 Gallons)
Pump: Myers High Head QP15, 1.5hp, 115V
Hose connections: Cam Lock quick connects -
1-1/2” hoses
Hand Truck: 600lb rating with pneumatic tires
Wiring: Liquid Tight metal on/off switch
Tubing: SDR11 HDPE
Connections: 2 - 3/4” connections for antifreeze and
discharge
Drain: one on the pump and the tank
Flushing & Charging a Pressurized Flow
Center
Once piping is completed between the unit, ow
center, and the earth loop, nal purging and
charging of the system is needed. A ush cart (at
least a minimum of 1.5 hp pump motor or larger)
is needed to achieve adequate ow velocity (2
fps in all piping) in the loop to purge air and debris
from the loop piping (unless the header manifold is
located inside and has isolation valves). All air and
debris must be removed from the system before
operation or pump failure could result. The ush
ports located on the ow center are access to the
piping system for the ush cart. See gure 7 for
connection details.
The 3-way valves on the ow center include
direction indicators on the valves which determine
the ow path. A 3/8” socket drive is required to
operate the 3-way valves. The valves will turn in
either direction, 360 degrees. Make sure during this
process that the valves are in the same position so
that air does not become trapped in the system.
Figure 9: Enertech Flush Cart
Section 5: Unit Piping Installation
Step 1: Flushing the Earth Loop
1. Connect ush cart hoses to ow center ush
ports using proper adapters #AGAFP.
2. Connect water supply to hose connection on
return line of ush cart.
3. Turn both 3-way valves on ow center to ush
ports and loop position.
4. Turn on water supply (make sure water is of
proper quality).
5. As the reservoir lls up, turn the pump on and off,
sucking the water level down. Do not allow the
water level to drop below intake tting to the
pump.
6. Once the water level remains above the water
outlet in the reservoir leave the pump running
continuously.
Figure 10: Flush Cart Pump Curve