DocNo.FM0805issueAPage33
41.INTERCOMUNITTESTMODE
Theintercomunit“TestMode”allowsallceilingpullcords,smoke detectorsandradiopendantsetc.tobetestedonaper‐flatbasis
withoutputtingacallonthesystem.OnceinTestModetheintercomwillbeepaseachdeviceisactivated,thesystemprinterwilllog
eachtest
withtheflatnumber,devicetype,time&date.
TheintercommustbeinaquiescentstatetoentertheTestMode,i.e.notinprivacymode,notinawaymode,nomessagewaiting,no
alarmcallinprogressandnotawaitingExtracarecancellation.
______________________________________________________________________________________________________________
ENTERTESTMODE:
1.Pressandholdthekeyforapprox5seconds untiltheintercombeepsonce‐thenreleasewithin2seconds.
2.TheintercomlightwillilluminateSTEADY WHITEanda7toneascendingscalewillplayonce.
3.Radiodevices(eg.personalpendants)mustbetestedfirst‐onceanyhardwiredceilingpullcordsorsmokedetectorsareactivatedno
furtherradiodeviceswillberecognised.
4.Theintercomwillbeeptwiceaseachdeviceisactivated.
______________________________________________________________________________________________________________
ENDTESTMODE:
1.TestModecanbeendedatanytimebypressingthekeyonce
2.Theintercomwillplay4descendingtonesandthe
STEADY WHITElightwillgoout.
3.Asafail‐safetheTestModewillendautomaticallyafter10minutes.
______________________________________________________________________________________________________________
Hardwiredmovementdetectors(PIR’s)areonlyreportedevery30seconds,thisistoallowmovementthroughthe
dwellingtogettothenextdevicewithoutre‐triggeringthePIRontheway.
Whenanyceilingpullcordisactivatedallpullcordreassurancelightswillbeilluminatedfor2seconds.
OnlyoneintercomcanbeinTestModeatanygiventime.
TestModecannotbeenteredviaaremoteintercom.
1.Pressandholdthe
key
forapprox5secondsuntil
theintercombeepsonce
thenrelease…
3.Thelightwillbe
STEADY WHITE
w
henTestModeisenabled
2.Sevenascendingtones
willsoundand…
Imageshowsastandard
intercom…
thesametestmodecan
beenteredona
combinedintercom.