Page 13
Owners Manual
The memory has a capacity to store 128,000 characters of printed
data. This represents 30+ days of normal operation and approximately
200 alarm messages. When the memory is full, the new data will
begin to overwrite the oldest data.
Note: Overwritten data cannot be retrieved.
Example of Printout after
START JOB
is pressed--
Alarm Condition
Once the containment pressure reaches the operating window, the
unit will be in normal operation and the alarms will be armed. Then
if containment pressure falls outside the operating window, the
following will occur:
1. Internal buzzer and AUX ALARM output will be activated and will
remain active until ALARM SILENCE is pressed.
2. The status bar will change to >>ALARM<< and begin flashing.
The STATUS LED will flash red.
3. Printer will indicate which alarm setpoint was exceeded. The
print/log rate will increase to the preset alarm rate. Printouts will
show the time followed by the current pressure reading.
When the containment pressure returns to within the normal
operating window, the unit will log and print NORMAL OP with a
time-stamp. The buzzer and AUX ALARM output will turn off. The
STATUS LED will return to a steady green. If the alarm was silenced
without rearming, it should be rearmed.
Alarm Silence, Disable and Rearming
The buzzer symbol on the Monitor Screen indicates whether the
audible alarm and AUX ALARM output are armed or disabled. The
alarm is always armed when the unit is first turned on. The alarm
silence function and AUX ALARM output are controlled by the
ALARM SILENCE key.
END JOB
Johnson Bldg
JOB SUMMARY
JOB NAME:
Johnson Bldg
JOB START:
11-26-03 05:38
JOB END:
12-01-03 17:09
TIME IN NORMAL OP:
5 days 10 hrs 23 mins
NUMBER OF ALARMS:
2
TIME IN ALARM:
16 mins 28 secs
START JOB
Wilson Remodel
Ending Current Job
Summary of Ended Job
Starting New Job