ENGINEERING
Page 26
Omniguard 4
damage. The printer symbol will be displayed with a JAM
message (see Section 4: Turning Printer On/Off). After the paper
jam is cleared, use the PRINTER ON/OFF key to turn the printer
back on.
Note: Do not apply oil or grease of any kind to the printer as this will
attract dirt and debris and could cause permanent damage to the
printer mechanism.
Problem: OMNIGUARD 4 unit does not enter normal operation
when turned on, and does not print.
Remedy:
For normal operation, the monitored pressure must be
between the Alarm 1 and Alarm 2 setpoints. When the unit is first
turned on, the containment pressure will not likely be within the
alarm setpoints, and the unit will not print or log the pressure
readings. The unit will begin printing and logging the pressure
readings only after it senses containment pressure has reached
the normal operating window.
Problem: The unit displays Date & TIme Not Set followed by
Factory Default after the power has been off.
Remedy:
The internal clock battery is discharged. Leave the unit
plugged in for 24 hours to recharge the battery. It will be
necessary to update the Date and Time settings. The internal
battery should last for 30+ days without recharging. It recharges
automatically any time the unit is plugged in. No other settings
need to be re-entered (they are saved in non-volatile memory and
do not require the internal clock battery).
Shipping & Repair
Please call the Engineering Solutions customer service department
for a return authorization. A number will be assigned to aid in
tracking your unit.
Send the entire unit, enclosing a brief explanation of the problem
along with your company name, address, phone number and name
of the individual responsible for the unit. The return authorization
number must be clearly marked on the outside of the box. No
CODs will be accepted. If the original packing materials are not
available, package the unit securely in a sturdy container with
enough padding to surround the unit on all sides. The unit should
not be able to be shift after packing. Engineering Solutions will not
be responsible for any damage which may occur.
Send to : Engineering Solutions, Inc.
6000 Southcenter Blvd, Suite 70
Tukwila, WA 98188-5742
(206) 241-9395 sales and service