EasyManua.ls Logo

epro MMS 6000 - Alarm visualization; Alarm outputs; Alarm latching; Switchover open-; closed-circuit mode SC-A, SC-D

epro MMS 6000
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MMS6110Directionforuse
Functiondescription Page34
4.4.3 Alarmvisualization
TworedLEDsonthefrontplateindicatethealarmstateoftherelevantchannel.Main
alarms(DANGER)areindicatedbyasteadyredlight,incaseofpre-alarms(ALERT)the
LEDsareflashing–provided,neitherthealarmblockingfunctionhasbeenactivatednor
digitalinput"externalblocking"isset.
4.4.4 Alarmoutputs
Thefouralarmoutputsareopencollectoroutputsandaregalvanicallyisolatedfromeach
otherandfromtheremainingcircuitsofthemodule.Thustheswitchingfunctionoftheoutput
isonlygivenwithanexternalsupply.
Channel1: MainalarmD1-C,D1-E(d26,d28), Pre-alarmA1-C,A1-E(b26,b28)
Channel2: MainalarmD2-C,D2-E(d30,d32), Pre-alarmA2-C,A2-E(b30,b32)
Ifseveralalarmoutputsaretobeconnectedinseries,(closed-circuitmode),ithastobe
takenintoaccountthateachoftheoutputstakesavoltagedropofmax.1.5V.Forthisrea-
son,notmorethanfouroptocoupleroutputs(C-E)shouldbeconnectedinseries,whendriv-
ingaREL020with24Vrelaysupply.WhenusinganREL010,upto8C-Eoutputsandwith
theREL054upto12C-E-outputsmaybeconnectedinseries.
4.4.5 Alarmlatching
FunctionAlarmlatchingmaybeactivatedonpropertysheetOutputchannel.Ifwith
thisfunctionanalarmisgenerated,itwillbelatchedandonlyberesetifthealarmcondition
is no longer true andif in menu Extras > commands command Reset latch chan-
nel1resp.channel2isgiven.
Withoutlatchingfunctionthealarmwillberesetassoonasthemeasuringvaluefallsbelow
theupperlimit(minushysteresis)orexceedsthelowerlimit(plushysteresis).
4.4.6 Switchoveropen-/closed-circuitmodeSC-A,SC-D
ThesignalstatesatthedigitalinputsSC-A(d24)forALERTalarmsandSC-D(z24)forthe
DANGERalarmsdefinethealarmoutputoperatingmode.
IncasetheSC-inputisopenorHIGH(+24V),therelevantalarmoutputsoperateinthe
opencircuitmode,i.e.atactivatedalarmsthetransistor'scollector-emitterlineiscon-
ductingandanexternalconnectedrelayactivated(seefig.4,connectiondiagram).
In case the SC- input is Low (0 V), the relevant alarm outputs operate in the closed-
circuitmode,i.e.atactivatedalarmsthetransistor'scollector-emitterlineisopen,thus
anexternalconnectedrelaywillbedeactivated(seefig.4,connectiondiagram).

Note:Whenthemoduleoperatesintheclosedcircuitmode,analarmwillbetrig
geredifthesupplyvoltagefailsorifthecardisremovedfromtherack.
Inthefollowingchaptersthereistalkaboutthedefaultstate(=noalarm)ofthealarmout-
puts.Defaultstatemeansanopencollector-emitterline(relaynotactivated)fortheopencir-
cuitmodeandaconductingtransistoroutput(relayactivated)fortheclosedcircuitmode.
Note:
ModulesoftypeMMS6110Caredeliveredfromthefactorywiththealarmoutputsfixed
totheclosed-circuitmode.Alarmoutputsofthesemodulescannotbeoperatedinthe
opencircuitmode.

Table of Contents