MMS6110Directionforuse
Configuration Page18
EntryfieldSubspeed
Ifthespeedcontrolledmodehasbeenchosen,thekeypulseswillbeusedtodetectthe
directionofrotationandforcontrollingthedataprocessingofthediagnosisfunction.Ifthe
speedfallsbelowthelimitvaluedefinedinfieldsubspeed,theprogramswitchesfromthe
speedcontrolledtothetimecontrolledmeasuringmode.
Sub-
Nom.
+Tol.
Over-.
speed.
-Tol.
timecontrol
timecontrol
speedinstationary*
speedinstationary*
speedstationary*
speedstationary*
*onlyifspeedcontrolledmodeisselected,
otherwisetimecontrolledmode
Diagram2
InputfieldsNominalspeedandSpeedtolerance
Ifthespeedcontrolledmodewithkeypulsewaschosenandifthespeediswithinthetole-
rancerangeofthenominalspeed,theprogramusesthestationarycontrol.Thismeans,the
valuesofthelistfieldsstationaryforrevolutionspercycleandmeasurementsperrevolution
are valid for displaying purposes. For speed values above limit subspeed and below the
lowerlimitofthetolerancerangeofthenominalspeed,aswellasintherangeabovetheup-
per tolerance of thenominalspeed andbelowthe max.speed limit, theprogram operates
withvaluesoflists„instationary“,refertodiagram2.
EntryfieldOverspeed
Iftheshaftspeedexceedsthevaluedefinedinthisfield,thediagnosisprogramswitches
fromthespeedcontrolledtothetimecontrolledmeasuringmode.
ListfieldsNa-NeOrder
BymeansoflistfieldsNa-Neordertheordernumberfortheorderanalysisinmenu
"display"canbedefined.Tomakeachoiceinthesefields,togglekey"SupportDiagnosis-
system"musthavebeensettoactive.
Thelistsindicatethemaximumavailableordernumberswhichdependsontheselected
numberofmeasurementsperrevolution(Omax=MPT/2.56).
2.3.5 PropertypagesOutputchannel1/2
Propertypage"Outputchannel"showsdialog"Parametersetting".Formoduleswith
combinedchannelsandonecharacteristicalvalue(modesSmaxandSppmax)onlyone