MMS6110Directionforuse
Configuration Page9
valueiscalculatedbycombinationoftheresultsofbothchannels,andwatchedonlimitex-
ceedings,thealarmfunctionwillbedisabledonly,ifbothchannelsindicatethemessage
"ChannelClearnotOK".
EntryfieldsTemperatureDangerandTemperatureAlert
Theinputfieldsfortemperaturealertalarmanddangeralarmshowthedefaultfactoryset-
tingsofthealarmvalues.IftheenvironmentaltemperatureofthemonitorexceedstheAlert
limitmeasuredbyabuilt-intemperaturesensor,theChannelClearLEDonthemonitorfront
startsflashingquickly.OnexceedingtheDangeralarm,thisisconsideredtobeamodule
fault,asaconsequencetheChannelClearLEDswilldistinguishandthealarmoutputsbe
suppressed(refertodetailedfunctiondescription--conditionmonitoringinsection4.5).
Thepredefinedlimitvaluesof65°Cand70°Cmaybemodifiedwithaccessauthorization
"Service".However,ithastobetakenintoaccountthatthedangerofmeasuringfaultsor
failuresofcomponentsincreaseswithhighertemperatures.
ParameterswitchSwitchonEX-mode
Thisfunctionhastobeactivated,iftheconnectedsensorsareinstalledinexplosionhazard-
ousareasandmustbeoperatedwithsafetybarriers.Theactivationofthisfunctioneffects
thatonpropertypage"channel"(channelconfiguration)theseriesresistanceofthesafety
barriersmustbeenteredintofield"seriesresistance".
2.3.3 PropertypageChannel
Thechannelconfigurationismadeinpropertypage"Channel".