EasyManua.ls Logo

epro MMS 6000 - Environmental conditions

epro MMS 6000
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MMS6110Directionforuse
TechnicalData Page45
Supplyinputs tworedundantinputs,decoupledviadiodes,
fornominal+24Vwithcommonground.
VoltageinputUB+/UN+ d2/z2
Commonground,0VU- b2
permissiblevoltagerange 18...31,2VdcaccordingtoIEC654-2class
DC4
Powerconsumption max6W,at24Vmax.250mA
Modulesystemsupply
Themodulesystemvoltagesrequiredfortheinternalsupplyarepermanently
checkedonlowvoltage.If"Lowvoltage"isdetected,anerrormessagewillbede-
tected(seesection6.2--channelsupervision).
Sensorsupply
forbothchannelsofthemodule.
Isolation decoupledandgalvanicallyisolatedtothe
othersystemvoltagesandtothesupplyvolt-
age.
tobeusednon-reactivelyinparallelwithother
modules
open-circuitandshort-circuitproof
Sensorsupplychannel1 SENS1-/SENS1+ b6/z6
Sensorsupplychannel2 SENS2-/SENS2+ b8/d6
Sensorsupplyvoltage 26,75VDC;tolerance±2%
Residualripple <20mVpp(atnominalcurrent20mA)
max.current 35mA
max.shortcircuitcurrent
0mAIshort5mA;
open-circuitandshort-circuitproof
6.6 Environmentalconditions
Applicationclass KTFaccordingtoDIN40040
Environmentaltemperature
Referencetemperature +25°C
Nominaloperatingrange 0...+65°C
Storage-,transporttemperature -30...+85°C
Relativehumidity 5...95
%non-condensing
Vibration AccordingtoIEC-68-2part6
Amplitude 0.15mmat10...55Hz
Acceleration 19,6mm/s
2
at55...150Hz