EasyManua.ls Logo

epro MMS 6000 - Channel supervision; Overload - supervision; Channel Clear LEDs; Channel Clear Outputs

epro MMS 6000
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MMS6110Directionforuse
Functiondescription Page36
4.5.1 Channelsupervision
Thedcvoltageoftheinputsignalischecked.Iftheinputvoltageexceedstheupperlimitof
thesensoroperatingrange+0,5V,enteredduringtheconfiguration,orifitfallsbelowthe
lowervalue-0,5V,achannelerrorwillbeindicated.
4.5.2 Overload-supervision
Iftheamplitudeofthedynamicsignalexceedsthemeasuringrangedefinedduringconfigu-
ration(plusapprox.1%),anOverloadmessagewillbegiven.
4.5.3 ChannelClearLEDs
Duringthecorrectmeasuringandsupervisionoperation,theChannelClearLEDsshowa
steadygreenlight.
TheChannelClearLEDsoperateindependentlyforeverychannel,i.e.duringachanneler-
rororduringthedelaytimeafterachannelerrorthiswillbeindicatedbytherelevantChannel
ClearLED.
Inprincipal,delaytimesandmodulefaultsaresignalledbybothLEDs.
Thetableinsection4.5.5showsthesignalizationdependingondifferentoperatingmodes.
4.5.4 ChannelClearOutputs
ThetwoChannelClearoutputsareopen-collectoroutputsandgalvanicallyisolatedfrom
eachotherandfromtheremainingcircuitsofthemodule.Thustheswitchingfunctionofthe
outputisonlygivenwithanexternalsupply.
channel1C1-C,C1-E(z26,z28) channel2C2-C,C2-E(z30,z32)
Duringcorrectmeasuringoperationsandwhenthesupervisionfunctiondoesnotindicatea
moduleerror,thecollector-emitterlineoftheChannelClearoutputtransistorsarecon-
ducting-i.e.theyoperateaccordingtotheclosedcircuitmode.Incaseofadisturbanceof
therelevantchannelorduringthedelaytimesafteranerror,thecollectoremitterlineofthe
outputisopen(seetableinsection4.5.5).Incaseofamodulefaultorduringdelaytimesaf-
teramodulefault,bothChannelClearoutputsareswitchedoff.
IfseveralCHANNELCLEARoutputsaretobeconnectedinseries,ithastobetakeninto
accountthateachoftheoutputstakesasaturationvoltageofmax.1.5V.Forthisreason,
notmorethanfouroptocoupleroutputs(C-E)shouldbeconnectedinseries,whendrivinga
REL020with24Vrelaysupply.WhenusinganREL010,upto8C-Eoutputsandwiththe
REL054upto12C-E-outputsmaybeconnectedinseries.
4.5.5 Effectofthemodulesupervision
FunctionChannelClear(CC)LEDs
Steadylight

OK-State
0 Off
_____________
Faultstate
FS Flashingslowly0,8Hz,2:1
____
Channelstate
FQ Flashingquickly1,6Hz,1:2
________
Modulestate

Table of Contents