EVCO | 06.08.2021 | AZ | 11
002_c-pro3OEM_ConnettoriSchedaGiorno_001_0.1_AZ
c-pro 3 OEM
AO4AO3 AO2 AO1 M9 M8
C1 NO1C2NO2 C3 NO3
M7 M6 M5 M4 M3
C4 NO4C5 NO5
M2 M1 GND 12V
NO6 C6 NC6
ITB GND A+
HV1HV1 HV2 HV2
B- C+ C-
PS PS
5V
2
1
ON
DIHV5 DIHV5
IN OUT
Pulse - EPB90V
114CP3OEE104
c-pro 3 OEM - Hardware manual
Electrical connections
WARNINGS FOR ELECTRICAL CONNECTIONS
Use cables of an adequate section for the current running through them
To reduce any electromagnetic interference connect the power cables as far away as possible from the signal cables
and connect to a CAN, RS-485 MODBUS and INTRABUS networks by using a twisted pair
If using an electrical or pneumatic screwdriver, adjust the tightening torque
If the device has been moved from a cold to a warm place, the humidity may have caused condensation to form inside.
Wait about an hour before switching on the power
Make sure that the supply voltage, electrical frequency and power are within the set limits
Disconnect the power supply before doing any type of maintenance
Do not use the device as safety device
For repairs and for further informations, contact the EVCO sales network; possible returns without label data will not be
accepted
Connectors description
Open frame version
Connector 8
Connector 1 Connector 2 Connector 4
Connector 3 Connector 5
Connector 6
Connector 7
Connector 1
Number Description
C1 K1 digital output common contact
NO1
K1 digital output normally open contact
(5 A res. at 250 VAC)
C2 K2 digital output common contact
NO2
K2 digital output normally open contact
(5 A res. at 250 VAC)
C3 K3 digital output common contact
NO3
K3 digital output normally open contact
(5 A res. at 250 VAC)
Connector 2
Number Description
C4 K4 digital output common contact
NO4
K4 digital output normally open contact
(5 A res. at 250 VAC)
C5 K5 digital output common contact
NO5
K5 digital output normally open contact
(8 A res. at 250 VAC)
Connector 3
Number Description
NO6
K6 digital output normally open contact
(16 A res. at 250 VAC)
C6 K6 digital output common contact
NC6 K6 digital output normally closed contact
Connector 4
Number Description
HV1 DI1 High voltage digital input
HV1 DI1 High voltage digital input
HV2 DI2 High voltage digital input
HV2 DI2 High voltage digital input
Connector 9
Connector 10