002_c-pro3OEM_ConnettoriSchedaGiorno_001_0.1_AZ
c-pro 3 OEM
AO4AO3 AO2 AO1 M9 M8
C1 NO1C2NO2 C3 NO3
M7 M6 M5 M4 M3
C4 NO4C5 NO5
M2 M1 GND 12V
NO6 C6 NC6
ITB GND A+
HV1HV1 HV2 HV2
B- C+ C-
PS PS
5V
2
1
ON
DIHV5 DIHV5
IN OUT
Pulse - EPB90V
114CP3OEE104
c-pro 3 OEM - Hardware manual
Electrical connections
WARNINGS FOR ELECTRICAL CONNECTIONS
– Use cables of an adequate section for the current running through them
– To reduce any electromagnetic interference connect the power cables as far away as possible from the signal cables
and connect to a CAN, RS-485 MODBUS and INTRABUS networks by using a twisted pair
– If using an electrical or pneumatic screwdriver, adjust the tightening torque
– If the device has been moved from a cold to a warm place, the humidity may have caused condensation to form inside.
Wait about an hour before switching on the power
– Make sure that the supply voltage, electrical frequency and power are within the set limits
– Disconnect the power supply before doing any type of maintenance
– Do not use the device as safety device
– For repairs and for further informations, contact the EVCO sales network; possible returns without label data will not be
accepted
Connectors description
Open frame version
Connector 8
Connector 1 Connector 2 Connector 4
Connector 3 Connector 5
Connector 6
Connector 7
Connector 1
Number Description
C1 K1 digital output common contact
NO1
K1 digital output normally open contact
(5 A res. at 250 VAC)
C2 K2 digital output common contact
NO2
K2 digital output normally open contact
(5 A res. at 250 VAC)
C3 K3 digital output common contact
NO3
K3 digital output normally open contact
(5 A res. at 250 VAC)
Connector 2
Number Description
C4 K4 digital output common contact
NO4
K4 digital output normally open contact
(5 A res. at 250 VAC)
C5 K5 digital output common contact
NO5
K5 digital output normally open contact
(8 A res. at 250 VAC)
Connector 3
Number Description
NO6
K6 digital output normally open contact
(16 A res. at 250 VAC)
C6 K6 digital output common contact
NC6 K6 digital output normally closed contact
Connector 4
Number Description
HV1 DI1 High voltage digital input
HV1 DI1 High voltage digital input
HV2 DI2 High voltage digital input
HV2 DI2 High voltage digital input
Connector 9