Connector 8
Number Description
AO4 Analogue output 4 (for 0-10 V or PWM)
AO3 Analogue output 3 (for 0-10 V or PWM)
AO2 Analogue output 2 (for 0-10 V or PWM)
AO1 Analogue output 1 (for 0-10 V or PWM)
DI4
Digital input
(dry contact and for pulse trains up to 2 KHz) DI4
DI3
Digital input
(dry contact and for pulse trains up to 2 KHz) DI3
IN7
Analogue input
(for PTC, NTC or Pt 1000 probes) AI7
can be congured also for dry contact digital input
DI12
IN6
Analogue input
(for PTC, NTC or Pt 1000 probes) AI6
can be congured also for dry contact digital input
DI11
IN5
Analogue input
(for PTC, NTC or Pt 1000 probes) AI5
can be congured also for dry contact digital input;
DI10
IN4
Analogue input
(for PTC, NTC or Pt 1000 probes) AI4
can be congured also for dry contact digital input
DI9
IN3
Analogue input
(for NTC probes, 0-5 V, 0-10 V, 0-20 mA or 4-20 mA
transd.) AI3
can be congured also for dry contact digital input
DI8
IN2
Analogue input
(for NTC probes, 0-5 V, 0-10 V, 0-20 mA or 4-20 mA
transd.) AI2
can be congured also for dry contact digital input
DI7
IN1
Analogue input
(for NTC probes, 0-5 V, 0-10 V, 0-20 mA or 4-20 mA
transd.) AI1
can be congured also for dry contact digital input
DI6
GND Reference (GND)
12VS Auxiliary power supply (12 VDC)
5VS Ratiometric transducer power supply 0-5 V (5 VDC)
Connector 7
Number Description
USB USB port, for device programming
Connector 9
Number Description
DIHV5 High voltage digital input; DI5
DIHV5 High voltage digital input; DI5
Connector 10
Number Description
IN Input Pulse digital outpuyt (230 VAC max. 30 W)
OUT Pulse digital output