FAAC E145 - J12 - Programmable Outputs - Electric Locks; J12 -J6 - Limit Switch and Gatecoder

FAAC E145
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E145 10 732784 - Rev. A
FCC2
FCC1
FCA2
FCA1
J6
26 25 24 23
GATECODER 1
GATECODER 2
FCC2
FCC1
FCA2
FCA1
J6
26 25 24 23
GATECODER 1
GATECODER 2
FCC2
FCC1
FCA2
FCA1
J6
26 25 24 23
J6 J6
J6
햲햳
ENGLISH
FCA1, FCC1 and GATECODER1 correspond to LEAF 1;
FCA2, FCC2 and GATECODER2 correspond to LEAF 2.
4.4 J12 - PROGRAMMABLE OUTPUTS - ELECTRIC LOCKS
20 OUT2
24 V
"
(Open Collector) programmable using the function
o2
(advanced programming);
default: indicator light
21 LOCK 1
Electric lock (12 V~ or 24 V
"
)
operated 2 sec before opening
of leaf 1
When BUS-2EASY encoder is disabled, the electric
lock is operated before each opening (in whatever
position the stopped leaf is in).
When BUS-2EASY encoder is enabled, the electric
lock is operated only before opening the closed leaf.
22 LOCK 2
Electric lock (12 V~ or 24 V
"
)
-
operated 2 sec before opening
of leaf 2
Other programming options are available by programming via a PC/MAC (see dedicated
instructions).
4.5 J12 -J6 - LIMIT SWITCH AND GATECODER
The limit switch contacts FCC1, FCA1, FCC2, FCA2 are all NC contacts.
They are programmable using the functions
FA
and
FC
(basic programming) ; default: disabled.
If no limit switches are used, you DO NOT need to jumper the limit switch contacts
FCC1, FCA1, FCC2, FCA2.
You can however use a single GATECODER (only for single leaf); in this case, you do
not need to jumper the unused inputs to the earth.
Fig. Limit switch and GATECODER connections (maximum configuration:
).