E145 21 732784 - Rev. A
ENGLISH
Display Basic Function
Default
F1
MOTOR 1 POWER:
You can adjust the maximum power of motor 1, which is the same during
both opening and closing.
01 = minimum power
50 = maximum power
If the power is modified, we recommend performing a new SETUP
- see the related paragraph.
If hydraulic motors are used, power must be programmed to maximum
level (
50).
25
F2
MOTOR 2 POWER (visualised only with the function Mn = 2):
You can adjust the maximum power of motor 2, which is the same during
both opening and closing.
01 = minimum power
50 = maximum power
If the power is modified, we recommend performing a new SETUP
- see the related paragraph.
If hydraulic motors are used, power must be programmed to maximum
level (
50).
25
En
ENCODER USE:
You can enable/disable the use of encoders (both BUS and GATECODER
encoders):
Y = encoders on both motors
no = encoders disabled
no
FA
LIMIT SWITCH WHEN OPENING (displayed only if function CF = 1 or
CF = PC):
Lets you set or disable use of the opening limit switch on swing-leaves .
In case of mixed configuration (CF = PC) this function works only
on the swing-leaves. The limit switch on the SLIDING leaf is required
and determines when the leaf stops.
no = opening limit switches disabled
01 = the limit switch determines the stopping of motion
02 = the limit switch determines the start of deceleration
After having changed the value of this function, SETUP is required:
the card will signal error
14 (configuration error) until the SETUP is
performed again or until the previous value is restored
no