TST Assembly instructions FUF2 / FU3F -A/-C/-F
FEIG ELECTRONIC GmbH page 85 of 114 TST_FUxF-A-C-F_Montageanleitung_EN_15
Possible reason for error
Motion detector 4
Communication of the control unit with the MWD BPC
motion detector was interrupted.
•Check the wiring of motion detector 4
•Restart the control unit or the motion detector
Motion detector 4
MWD BPC customer coding failed
•customer coding of the MWD BPC is not compatible with the control unit.
•MWD BPC may already be encoded. Replace with an unpaired device
Motion detector 4
MWD BPC wrong customer coding
•customer coding of the MWD BPC is not compatible with the control unit.
•Replace MWD BPC with unpaired or correctly paired
Motion detector 4
MWD BPC software update failed.
• If the error occurs at 0% the update file might be incompatible to the MWD
BPC.
• If the error occurs during the transfer of the update, perform the update
again, if it occurs several times, replace the device
Internal emergency stop „push-button“ or watchdog
(monitor) triggered (watchdog only for FUS, FUN,
FUE, FU3E, FU3P)
• Emergency stop chain was interrupted starting at input „internal--Stop“
without parametrizing mode having been selected
• Internal parameter or EEPROM checks defective, pressing the STOP button
provides additional information about the cause (only valid for FUS, FUN, FUE,
FU3E, FU3P)
External emergency stop 1 triggered
• Emergency stop chain was interrupted from emergency stop input 1
External emergency stop 2 triggered
• Emergency stop chain was interrupted from emergency stop input 2
• During opening an obstacle has recognized
• During closing an obstacle has recognized
Short circuit detected on edge input
• Short circuit detected on edges with normally closed contact
• The light beam of the optical edge is interrupted
• Jumper for 1K2 / 8K2 is wrong set
Number of trips of the Safety input D, normally this is
the integrated safety edge evaluation, has reached
set limit (configurable in P.46E)
• Parametrized, maximum number of trips of the safety input D during a door
cycle was exceeded → Close the door in jog mode to reset
• Check the set number of trips in P.46E
Redundancy error with short circuit
• One of the processing channels for short circuit detection does not react
identically with the second channel → Controller board defective, if no other
error message F.3xx is shown
• Dynamical optical safety edge connected but not set in Parameter P.460
Interruption on edge input
• Connection cable defective or not connected
• Termination resistor incorrect or missing
• Jumper 1K2 / 8K2 incorrectly set