Pump speed is controlled according to collector tempera-
ture rather than (usual) temperature difference. The aim is
to maintain constant collector temperature, adjustable with
parameter “Tcolset“.
Target temperature:
Solar/Options/Target tem.
selection: “Yes“, “No“
factory setting: “No“
if you select “Yes“:
Solar/adj. values/tcolset
adjustment range: 20 ... 110 °C
factory setting: 65 °C
Parallel relay:
Solar/Options/Par. Relay
selection: “Yes“, “No“
factory setting: “No“
If the solar circuit pump is switched-on, this relay is activated
in parallel.
In 2-collector systems which are working with 2 pumps, the
parallel relay is activated if one of the 2 pumps is activated.
CS-Bypass:
Solar/Options/CS-Bypass
selection: “Yes“, “No“
factory setting: “No“
if you select “Yes“:
Solar/adj. values/CS-Byp.
adjustment range: 100 ... 500 W/m
2
factory setting:: 200 W/m
2
If the irradiation exceeds the adjusted value CS-bypass, the
collector circuit is operated. It is switched off when the
irradiation has fallen below the value „CS-bypass“ for at
least 2 minutes.
The collector circuit is operated with minimum pump
speed.
2-collector systems:
If a loading of the stores is carried out in these systems, the
function is switched-off.
Collector emergency shutdown:
Solar/adj. values/Tcolsec
adjustment range: 110 ... 200 °C
factory setting: 130 °C
hysteresis:10K
At high collector temperatures (depending on system pres-
sure or antifreeze concentration etc.) the systems is shut
off. This means that solar loading is not possible.
If the adjusted temperature threshold „Tcolsec“ is excee-
ded, the corresponding collector will no longer be used for
loading.
Afterheating suppression:
Solar/Options/ah suppress.
selection: “Yes“, “No“
factory setting: “No“
if you select “Yes“:
Solar/Expert/ah suppress.
adjustment range: St 1 ... St 4
factory setting: St 1
This function is activated if a previously selected solar store
(parameter designation: “AH suppress.“ in the menu solar
expert) is being loaded.
Solar loading means that store loading is only carried out for
energy supply and not for cooling purposes etc.
collector blocked
A collector is considered to be blocked, if either the sensor
is defective or the emergency shutdown temperature is
reached.