| 40
ECOTRONIC Plus
© Ferroli 08164 ECOTRONIC Plus.monen.indd
System warning DT too high“
Expert/DT too high
selection: “Yes“, “No“
factory setting: “Yes“
This message is shown, if solar loading has been carried out
for a period of 20 minutes with a differential higher than
50K.
The message function can be deactivated by selecting
“No“.
System warnin
g “Non-ret. valve“
Expert/non-ret. val.
selection: “Yes“, “No“
factory setting: “Yes“
This message is shown if between 11 p.m. and 5.00 a.m. the
collector temperature is higher than 40 °C or a store is
loaded because of a high temperature difference.
The message function can be deactivated by selecting
“No“.
Message relay (error message)
Expert/message rel.
selection: “Yes“, “No“
factory setting: “No“
Activate this function by selecting “Yes“. If the controller
detects a fault, the message relay is energised (e.g. for signal
lights).
These errors are:
• Sensordefective
• Real-time-clock(RTC)defective
• Storagemodule(EEPROM)defective
Please note that a message caused by one of the plausibility
controls (non-return valve, DT too high) does not activate
the relay.
Chimney sweeper
Expert/chimney
selection: “Yes“, “No“
factory setting: “No“
Expert/chimney sweeper
This function is used for activating a given relay state when
required.- e.g.flue gas measurement if the system controls
a boiler. Activate this function by selecting “Yes“.
Adjust the required relay status in the chimney sweeper
menu (expert / chimney sweeper).
If the chimney sweeper function is activated,chimney
sweeper“ is indicated in the main menu.
Sensor offset
Expert/Sensors/CS-Type
selection: A, B, C, D, E
factory setting: E
Expert/Sensors/CS-Adjust
Expert/Sensors/CS-Offset
Expert/Sensors/Sensor 1 (...12)
adjustmentrange:-5,0...5,0K
factorysetting:0,0K
Adjust the CS-type in this menu. The CS-type should be
matched to the code letter printed on the CS type label.
The CS-offset adjustment should be carried out with the
irradiation sensor disconnected.
Furthermore, an offset for sensors 1 ... 12 can be carried
out.
4.4 Menu: Expert