5 Function module F23
Festo – P.BE-CPX-FB23-24-EN – 1305a – English 75
5.5.1 RUN/PAUSE and STOP of the master
In the STOP mode of the CC-Link master ( e.g. by interruption of c ommunication) the state of the
outputs in bit range (RY) and word range (RWw) is dependent on the DIP switch setting HOLD/CLEAR
( section 2.4.9).
The following table shows the reaction acc ording to CC-Link specifications:
CC-Link master status
DIL switch setting
CLEAR HOLD
RUN/PAUSE Normal operation (Refresh)
STOP The outputs (RY/RWw) are reset. The outputs (RY/RWw) retain their
status.
Tab. 5.7 RUN/PAUSE and STOP of the master
Note
With STOP the enable bits of the analogue outputs ( co ntrol) are set to 0.
The analogue outputs will then also be set.
5.6 General notes on diagnostics and error handling
The instructions and descriptions for diagnostics and error handling in the sections 4.1
and 4.5.2 are also valid for the function module F23.