A Technical appendix
76 Festo P.BE-CPX-FB23-24-EN 1305a English
A Technical appendix
A.1 Technical data
General Function module
F24 F23
General technical data CPX system description ( P.BE-CPX-SYS-…)
Protection class according to E N 60529
With fieldbus plug FBS-SUB-9- GS-2X4POL-B
With connection block FBA-1-KL-5POL or oth-
er field bus plugs
CPX terminal fitted completely, plug connector as
per Accessories plugged in or fitted with
protective cap
IP65/IP67 (fitted c ompletely)
IP20
Protection against electric shock
(protection against direct and indirect contact in
accordance with I EC/DI N 60204-1)
By means of PELV power circuit
(Protected Extra Low Voltage)
Module code (CPX-specific)
Remote I/O
Remote Controller
Module identifiers (CPX-MMI-1, CPX-FMT)
Remote I/O
Remote Controller
206
157
FB24-RIO
FB24-RC
206
157
FB23-RIO
FB23-RC
Power supply
Operating voltage / load voltage CPX system description
(P.B E-CPX-SYS-…)
Current consumption bus node CPX-FB23-24
Internal current consumption at 24 V (internal elec-
tronics):
From operating voltage supply for electron-
ics/sensors (U
EL/SEN
)
Typically 70 mA
Galvanic isolation
Between bus interface and CPX periphery
(powe r supplies)
Yes