Twinflex V3 Control Panel Engineering and Commissioning Manual
28
Lamp Test (all panels).
1. Press and hold the button
marked ‘LAMP TEST
The buzzer will sound immediately and after 5
seconds all the indication lights will be switched on.
Release the ‘LAMP TEST’ and both the indication
lights and the buzzer will stop.
To Enter Access Level 3 ‘Engineer’ mode (all panels) Ensure control panel is in Access Level 2 (user)
1. Press ACCESS’ and then 5244 The buzzer will be heard continually until the code
is successfully entered, the ‘CONTROLS
ENABLED’ light will flash and the buzzer will sound
intermittently.
If an incorrect code is entered, simply start the
above sequence again.
Access Level 3 (Engineer)
In the ‘Engineer’ state the panel is still active in detecting fire and fault conditions and will sound the alarm
sounders when it is triggered. The ‘User Controls’ however, are disabled and the controls described below
replace the functions marked on the control panel overlay.
At this point the control panel indication should include a steady green ‘POWER’ light and a flashing yellow
‘Controls Enabled’ light, unless any fire or fault conditions are detected. The buzzer will also sound
intermittently.
To Exit ‘Engineer’ mode (all panels)
1. Press ACCESS The ‘CONTROLS ENABLED’ light will change from
the flashing state to a steady state.
The intermittent buzzer tone will stop.
NOTE: On the 8 Zone Panel, it is best instead to use the keyswitch (turn the keyswitch anticlockwise and
return to normal operation).