136
- Error code
- Error message
- LED status
Name of Alarm and Cause Solution
- E058
- Internal error
-
Yellow LED
Error in the check of Pin vs Pout:
The error occurs if the difference between
the measured value of input power and
that of output power is greater than the limit
imposed internally to the inverter.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- E074
- Internal error
-
Yellow LED
Communication error inside the inverter:
The alarm occurs when there are
communication problems between the
control devices inside the inverter.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- E077
- Internal Error
-
Yellow LED
Error in the system configuration:
Error inside the inverter
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- E078
- Riso Test fail
-
Yellow LED
Riso test error:
Problem detected during the Riso test
phase.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- E079
- Wrong Sequence
-
Yellow LED
Incorrect Phases connection
(Only triphase models) The phases have
not been connected correctly to the AC
output
• Invert two of the phases of the network wiring to the AC
terminal block of the inverter.
- E084
- BackFeed OC
-
Yellow LED
Return current to photovoltaic field:
The error occurs if the input voltage is
particularly low (typically in the evening in
conditions of low irradiation) and indicates
a return current from the inverter to the
photovoltaic panels).
If the error occurs in the evening or in conditions of low
irradiation, it must not be considered a problem but a protection
intervention for the photovoltaic field.
- If the error occurs with good irradiation conditions, switch
the inverter off and back on again; if the error persists, contact
customer assistance.
8.10.3 Power limitation messages
The equipment can signal possible output power limitations which may occur on the basis of:
settings made by the user
settings required by the grid standard of the country of installation
protective devices inside the inverter
The limitation messages can only be verified on the Web User Interface on “Status Summary” section (“MAIN menu”).