EasyManua.ls Logo

Fire-Lite ACC-25 - All-Call During FACP Activated Alarm; All-Call During Manual Evacuation;Alert; All-Call Emergency Page Using Local Microphone; All-Call Emergency Page Using Optional Remote Microphone

Fire-Lite ACC-25
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
72 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Operating Instructions Operation
from the local/integral microphone will override paging operations from the optional Remote
Microphone. Refer to Section “S3 DIP Switch Settings on ACC-25/50 Motherboard (ACC-MCB)”
on page 37 and the ACC-25/50DA Manual, Document #52265, for additional information.
All-Call General Page Using Local Microphone
Selecting the All-Call push-button and pressing the local microphone push-to-talk switch will
direct paging audio to all speaker circuits.
All-Call General Page Using Optional Remote Microphone
Pressing the remote microphone push-to-talk switch will direct paging audio to all speaker circuits,
and illuminate the All-Call and Audio On/Off buttons on the keypad. Note that Remote Micro-
phone All-Call functionality is DIP switch programmable for the ACC-25/50. Set the DIP switch to
ON. Refer to Section “S3 DIP Switch Settings on ACC-25/50 Motherboard (ACC-MCB)” on
page 37.
All-Call Emergency Page Using Local Microphone
Selecting the All-Call push-button and pressing the local microphone push-to-talk switch will
interrupt
the tone/voice message and direct paging audio to all speaker circuits. The system will
revert back to the tone/voice message if the microphone key is held for more than 3 minutes.
All-Call Emergency Page Using Optional Remote Microphone
Pressing the remote microphone push-to-talk switch will interrupt the tone/voice message and
direct paging audio to all speaker circuits, and illuminate the All-Call and Audio On/Off buttons on
the keypad. The system will revert back to the tone/voice message if the remote microphone key is
held for more than 3 minutes. Note that Remote Microphone All-Call functionality is DIP switch
programmable for the ACC-25/50. Set the DIP switch to ON. Refer to Section “S3 DIP Switch Set-
tings on ACC-25/50 Motherboard (ACC-MCB)” on page 37.
All-Call During FACP Activated Alarm
Selecting the All-Call push-button will direct the FACP activated tone/voice message audio to all
speaker circuits.
All-Call During Manual Evacuation/Alert
Selecting the All-Call push-button and pressing one of the Message push-buttons will direct the
tone/voice message audio to all speaker circuits.
All-Call With Distributed Audio Panels
Selecting the All-Call pushbutton activates the Master Command Bus (ACC-25/50 ONLY), which
triggers all Distributed Audio Panels. All-Call Paging or Messaging is generated over all speaker
circuits.
4.5.7 All-Call: ACC-25/50ZS & ACC-25/50ZST
The ACC-25/50ZS & ACC-25/50ZST uses the Zone Page Module (ACC-ZPM) for control of
audio zones. Pressing the All-Call push-button will activate all non manually deactivated speaker
circuits on the Zone Page Module, activate the Audio Amplifier Module (ACC-AAM25) output(s).
The S3 DIP switches on the ACC-25/50ZS & ACC-25/50ZST motherboard must be set for single
zone operation. Note the All-Call paging from the local/integral microphone will override paging
from the RPJ-F and Remote Microphone. Paging from the RPJ-F will override paging operations
from the Remote Microphone. Refer to Section “S3 DIP Switch Settings on ACC-25/50 Mother-
board (ACC-MCB)” on page 37.
All-Call General Page Using Local/Integral Microphone
Selecting the All-Call push-button and pressing the local microphone push-to-talk switch will
direct paging audio to all Zone Page Module speaker circuits.

Table of Contents