DDM module Default values
Threshold set Set #1
Input Channels
Enablement Enabled
Channel Label See note 1 (**)
Assigned zone Address related (see
Zone assignment)
Use zone setting Yes
TSM module Default values
Label See note 1(**)
Enablement Enabled
LED blink On
External power On
Input function Door monitoring
Loop monitoring Off
Door monitoring event Fault
Monitoring time 30s
Input Channels
Enablement Enabled
Channel Label See note 1(**)
Assigned zone Address related (see
Zone assignment)
Operating mode Style C
Callout Description
NO Output channel
Enablement Enabled
Channel Label See note 1 (**)
Trigger zone #1 Address related See
Zone assignment
Trigger zone #2 None
Trigger point #1 None
Trigger point #2 None
Trigger point #3 None
Silenceable Yes
Trigger on event Zone Alarm
Delay from alarm Off
Zones Default values
Label Zone AAA(*)
Enablement Enabled
Walk test Off
Detector warning Off
Delay to alarm Off
Drift compensation Off
Double knock Off
Smoke verification Off
Delay to alarm duration 0s
On board
programmable
outputs Default values
Enablement Enabled
Channel label Tttt y (see note 2 (****))
Trigger zone #1 None
Trigger zone #2 None
Trigger zone #3 None
Trigger zone #4 None
Trigger point #1 None
Trigger point #2 None
Trigger point #3 None
Silenceable Yes
Active on disablement
(where applicable)
Off
Trigger on event None
Delay from alarm Off
General options Default values
Investigation delay 300s
Main fault delay 1m
Delay to alarm 60s
Silence duration 60s
Reset 2s
Loop 1 wires 4 wires
Loop 2 wires 4 wires
Loop 3 wires 4 wires
Day/Night mode Day mode
SC1 disablement Enabled PSTN
Communicator
enablement
Not operative
FC503 and FC506 Addressable Fire Control Panels 71