EasyManua.ls Logo

Flow HYPLEX - Troubleshooting Table: System Behavior

Default Icon
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© Flow International Corporation M-416 | 37
CHAPTER 3
Maintenance & Troubleshooting
My UHP pressure seems to change depending on the state of the on/off valve (whether it's on or off).
Some degree of pressure change (2000-3000 psi [138-207 bar]) with the switching of the on/off valve is normal.
My pump does not start.
Pump not wired.
Check that operator-supplied service dis
-
connect is on and all fuses are properly
sized and functional
Check that the motor starter disconnect is
turned on
Check for loose wiring. Call a certified
electrician.
Tripped circuit breaker in control box. Call Flow Technical Service.
My pump starts but immediately shuts down.
Crankcase oil temperature too high (can be
validated through FlowMaster Advanced
Diagnostics).
Ensure proper oil level
Verify electrical sensor is functioning prop-
erly and replace if necessary
Replace crankcase if all other options have
been exhausted
Low inlet water pressure.
Validate proper operation of inlet solenoid,
pressure gauges and switches; replace if
necessary
Verify adequate operator-supplied water
source
Check fuses
Motor overload shutdown has been tripped. Check with a certified electrician.
My inlet water gauges are not reading pressure.
Operator-supplied water not on, or supply
pressure is insufficient.
Turn water on, inspect water supply pressure.
Failed inlet pressure gauges or gauge snubbing
orifices are clogged.
Replace gauges or clean snubbing orifices.
Inlet solenoid valve not opening.
Verify that an open signal is sent to the
valve
Check wiring and tighten or replace
Check fuses
Kinked or obstructed gauge line. Re-position the line or replace if damaged.

Table of Contents

Related product manuals