4.3.3 SEALING CONDUITS / ENCLOSURE
For FM Group A,B,C,D : “SEAL ALL CONDUIT ENTRIES WITHIN 18 INCHES”.
For CSA group B,C,D: “SEAL ALL CONDUIT ENTRIES WITHIN 18 INCHES”.
For CSA group A: FOR GROUP A SEAL AT ENCLOSURE WALL”
4.3.4 FLAMEPROOF JOINTS
Clause 5: EN/IEC 60079-1:2007 (Use certified / Ex d cable glands).
All flameproof joints are designed for:
- Volume 500 < V ≤ 2000 cm³;
- Group IIC enclosures.
There are 4 types of joints between inner and outside of the E-type enclosure which are flameproof:
1. The cement between glass and cover (length 10mm)
2. Thread between body/cover M100x1.5 (Tolerance 6g/6H min. 8 full threads engaged)
3. Thread for conduit opening left and right:
M20 x 1.5, M25 x 1.5, (for metric: Tolerance 6g/6H min. 8 full threads engaged);
½ NPT, ¾ NPT. (for NPT: Tolerance ANSI/ASME B1.20.1).
4. The process opening:
M20 x 1.5, M25 x 1.5 (for metric: Tolerance 6g/6H min. 8 full threads engaged);
½ NPT, ¾ NPT, 1 NPT (for NPT: Tolerance ANSI/ASME B1.20.1);
All NPT threads (cable entry openings) are in accordance with ANSI/ASME B1.20.1.
All Metric threads (cable entry openings, thread between body and cover and threaded
holes for feed thru capacitors) are in accordance with fit class 6g/6H (ISO 965-1 + 965-3).
When installed according to this manual, this product will meet the directives and standards as listed
in Appendix A of this manual.
4.3.5 CONNECTION TO OTHER ENCLOSURES
The E-series can be connected to another Ex d enclosure following the compulsory conditions
below:
The part which is used for the connection between the two volumes must be Ex d certified;
The connected enclosure must be Ex d certified with its own electrical equipment inside
(i.e. pickup coil or other sensors);
For the short cylinder version, the volume of empty space inside this added volume must not
represent more than 13,5 cm
3
;
There may be no generation of heat in the added enclosure;
There may be no added electrical energy in the added enclosure; any energy which comes from
the E-series is already taken into account in the E-series certificate.

Other manuals for Fluidwell E119-P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluidwell E119-P and is the answer not in the manual?

Fluidwell E119-P Specifications

General IconGeneral
BrandFluidwell
ModelE119-P
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals