EasyManua.ls Logo

Fluke 6200 - Warnings: Read Before Using

Fluke 6200
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Users Manual
Safety Information
3
Warnings: Read Before Using
To avoid possible electric shock or personal injury,
follow these guidelines:
If the tester does not power up immediately after
connecting it to the mains outlet disconnect and
verify that the mains outlet is correctly wired.
Use the tester only as specified in this manual, or the
protection provided by the tester might be impaired.
The tester shall not be used for measurements in
electrical installations.
When conducting tests do not touch the appliance as
some tests involve high voltages and high currents.
Do not use the tester around explosive gas, vapour or
dust, or in wet environments.
Inspect the tester before using it. Do not use the
tester if abnormal conditions of any sort are noted
(such as a faulty display, broken case, etc.).
Use only test leads and probes supplied with the
tester, or indicated by Fluke as suitable for the tester.
Inspect the test leads for damaged insulation or
exposed metal. Check test lead continuity. Replace
damaged leads before using the tester.
When testing, always be sure to keep your fingers
behind the safety barriers on the test leads.
Never open the tester’s case because dangerous
voltages are present. There are no user replaceable
parts in the tester.
Have the tester serviced only by qualified personnel.
The tester must be properly earthed. Only use a
supply socket that has a protective earth contact. If
there is any doubt as to the effectiveness of the
supply socket earth, do not connect the tester. Do not
use a two-conductor adapter or extension cord; this
will break the protective ground connection.
The tester has been set for a nominal 240 V ac – 50 Hz
operation, it must never be connected to a higher
voltage.
The tester may only be connected to a correctly wired
mains socket protected for a maximum current rating
of 13 A.
The mains supply is never to be connected to the IEC
lead test connector.
When carrying out Earth Bond tests, regularly zero
the earth bond test lead.
Under certain test conditions the test socket may
have mains potential with a maximum current of 13 A.
If the tester continuously emits a two tone sound, you
should unplug it immediately as this indicates a
dangerous condition.

Related product manuals