Step 8: Electrical Wiring
aGate terminal information and wiring requirements
Terminals: Copper alloy
Surface Finish: Tinning
Hex head screw: 5/8-18 UNF
Stripping Length:1in
Applicable Cable: 4AWG~250 MCM CU
Wiring Torque: 3/0AWG~250 MCM 275LB-IN
4AWG~2/0AWG 110LB-IN
DANGER: The wiring should comply
with NFPA 70 and local laws and
regulations.
Terminals: Copper alloy
Surface Finish: Tinning
Hex head screw: 5/8-18 UNF
Stripping Length1in (upper layer)
2in (lower layer)
Applicable Cable: 4AWG~250 MCM CU
Wiring Torque: 3/0AWG~250 MCM 275LB-IN
4AWG~2/0AWG 110LB-IN
DANGER: The wiring should comply
with NFPA 70 and local laws and
regulations.
Terminals: Aluminum alloy
Surface Finish: Tinning
Hex head screw: 7/16-20 UNF
Stripping Length0.8in
Applicable Cable: 14AWG~2/0AWG CU
Wiring Torque: 3AWG~2/0AWG 110LB-IN
14AWG~4AWG 35LB-IN
Hex head screw: 1/4-28 UNF
Stripping Length0.4in/0.8in
Applicable Cable: 14AWG~4AWG CU
Wiring Torque: 14AWG~4AWG 26LB-IN
DANGER: The wiring should comply
with NFPA 70 and local laws and
regulations.
Terminals: Aluminum alloy
Surface Finish: Tinning
Hex head screw: 5/8-18 UNF
Stripping Length1in
Applicable Cable: 4AWG~250 MCM CU
Wiring Torque: 3/0AWG~250 MCM 275LB-IN
4AWG~2/0AWG 110LB-IN
Hex head screw: 7/16-20 UNF
Stripping Length1in
Applicable Cable: 14AWG~2/0AWG CU
Wiring Torque: 3AWG~2/0AWG 110LB-IN
14AWG~4AWG 35LB-IN
Hex head screw: 1/4-28 UNF
Stripping Length: 0.6in
Applicable Cable: 14AWG~4AWG CU
Wiring Torque: 14AWG~4AWG 26LB-IN
DANGER: The wiring should comply
with NFPA 70 and local laws and
regulations.