EasyManua.ls Logo

Freestyle 2 Series - Page 5

Freestyle 2 Series
136 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 1 REQUIRED minimum clearances
(
all dimensions are in inches)
Part number 550-142-950/0122
5
FreeStyle
®
series
2
wall mount gas-fired water boiler boiler manual
2 Prepare boiler location continued
Provide clearances from
combustible materials — REQUIRED
1. See Figure1 for REQUIRED minimum clearances. ALL
installation must provide at least these minimums.
2. Hot water pipes — at least ½” from combustible materials.
3. Vent pipe — at least
3/16” from combustible materials.
4. See Figure1 for service clearance minimums.
If the unit is enclosed in a cabinet or mounted
alongside, a space must be provided for remov-
ing the casing and for normal maintenance
operations. e minimum measurements to be
respected are given in Figure1.
Provide clearances for service
access — RECOMMENDED
1. See the table in Figure1 for recommended service clearances.
2. If you do not provide minimum service clearances shown, it
might not be possible to service the boiler without removing
it from the space.
3. Clearance D, Figure1 allows for the installation of piping as
shown in Figure5,page9, plus a union, close nipple and
elbow.
Clearances
A Provide combustion air/ventilation openings per Fig-
ure23,page20 or as otherwise directed in this manual or by
applicable codes.
If the installation does not provide the minimum clear-
ances, then the enclosure MUST HAVE air openings located per
Figure23,page20. Each of these air openings must have free area
of at least 1square inch per 1,000 MBH of boiler input.
B Le side clearance to combustibles = 1.0 inches minimum
C Top of boiler clearance to combustibles = 12.0 inches minimum
D Right side clearance to combustibles = 1.0 inches minimum
E Bottom of boiler clearance to combustibles = 12 inches minimum
(must be 18inches above oor for garage installations)
F Clearance in front of the boiler = 12.0 inches, but 36 inches
minimum required for service
H Vent pipe must be minimum 3/16 inch from combustibles. Open-
ing in combustible wall, oor, ceiling or roof must be 3/8” larger
than ue pipe diameter, tted with galvanized steel thimble, or
larger if required by codes or as specied by vent pipe manufac-
turer.
ADDITIONAL service clearance may be
needed, depending on how piping is routed
to the boiler.
A Provide combustion air/ventilation openings per Figure23,page20 or as
otherwise directed in this manual or by applicable codes. NOTE: If the
installation does not provide the minimum clearances in this illustration,
then the enclosure must have air openings located and sized per Fig-
ure23,page20.
B Le side service clearance = 36 inches minimum
C Service clearance above top of boiler = 24 inches minimum
D Right side service clearance = 24 inches minimum
E Service clearance below the boiler = 36 inches minimum
F Service clearance in front of the boiler = 36 inches minimum
Minimum
required
for
Combustion
A Minimum 1.00”
B Minimum 12.00”
C Minimum 12.00”
D Minimum 12.00”
Recommended
for
Service
A Minimum 36.00”
B Minimum 36.00”
C Minimum 24.00”
D Minimum 36.00”

Table of Contents

Related product manuals