34 PB
OPERATION
Heat Control Operation - Electric Heat Only (KEQ08A11A)
WhenintheHeatmode,withandwithoutFanModeAuto(Fancycling):
IftheindoorambienttemperatureisbelowtheHeatDemandThreshold(HeatSetPointminus1.5˚F),turnon
electricheat.IfAmbientis0.3˚FabovetheHeatSetPointturnofftheelectricheat.
System Mode Auto
Thismodeprovidesautomaticchangeoverbetweencoolandheat.Theautomoderunsbasedontheroomambient
temperaturevs.theDemandThresholds.ItisonlyavailableinHeat-CoolUnit.
Notes:
Thereisabufferzonebetweenthecoolandheatsetpointswherenoheatingorcoolingisallowedtooccur.Itis
criticalthattheCoolDemandThresholdbegreaterthantheHeatDemandThresholdbyaminimumof3°while
intheAutoSystemMode.Forexample,ifauserentersavaluefortheAutoCoolingSetPointthatviolatesthe
minimum3°rule,theAutoHeatingSetPointwilladjustaccordingly.
Automatic Change Over Delay (Cool with Heat Units)
Thechangeoverdelayensuresthatanysystemheatingorcoolingovershootdoesnottriggeranoppositedemand
cycle.Thechangeoverdelay=15min.Thistimerblockstheoppositedemandcyclefromrunninguntilthetimer
expires.Asanexample,ifthelastdemandwasacoolcycle,andanothercoolcycleisrequested,thetimerwillnot
blocktherequest.However,ifthelastdemandcyclewasacoolcycle,andheatcycleisrequested,thetimerwill
blocktherequestuntilthechangeoverdelayisexpired.
Compressor Lock Out Time
Thelockoutfeatureensuresthatthecompressorisde-energizedforaperiodoftime.Thetimervariesrandomly
from180to240seconds
Thecompressorlockoutisinitiatedeverytimethecompressoris“off”dueto:
(1) Satisfying the temperature set point
(2) Changing mode to fan only or heat
(3) Turning the unit off
(4) Controlisrstpluggedinorpowerisrestoredafterfailure
(5) Linepowerisrestoredfromabrownoutcondition
Cooling Fan Delay
Fancycle/Automodeonly
WhenunitcyclescoolingON–startsthefan5secondsEARLY.WhenunitcyclescoolingOFF–DELAYSthefanoff
for30seconds.