126
Status
504
Communication with Solar Net not possible
Description Fronius IG Plus address has been assigned twice
Remedy Change Fronius IG Plus address (section: ‘The Setup
Menu’)
Description The Solar Net components required are in the Froni-
us IG Plus: However, no communication is possible
Remedy Status message will disappear after changing the
Fronius IG Plus address
505
EEPROM defective
Description Data has been lost from the Setup menu
Remedy Error corrected automatically
506
EEPROM defective
Description Data has been lost from the ‘Total’ menu
Remedy Error corrected automatically
507
EEPROM defective
Description Data has been lost from the “Day”/”Year” menu
Remedy Error corrected automatically
508
Fronius IG Plus address contains an error
Description The address for data communication is no longer
stored
Remedy Reset address
509
No power feed for 24 h
Description e.g.: Solar modules covered with snow
Remedy e.g.: Remove snow from solar modules
510
EEPROM defective
Description SMS settings have been reset to their defaults
Remedy Reconfigure SMS if necessary
511
EEPROM defective
Description Sensor card settings have been reset to their defaults
Remedy Reconfigure measuring channels if necessary
Messages -
Class 5