90
Menu Options
in the Setup
Menu
(continued)
LIGHTMODE
Initial setting for display illumination.
Unit -
Setting range AUTO / ON / OFF
Factory setting AUTO
AUTO: The display illumination is switched off if no key is pressed for
30 seconds.
ON: The display illumination remains on permanently while power is
being fed into the grid.
OFF: The display illumination is permanently switched off.
Important! The ‘LightMode’ setting only relates to the display’s back-
ground illumination. There is no need to switch off the display itself as it
uses only a small amount of energy (less than one mW (1/1000 W)).
CASH
Currency and charge rate setting for the energy fed into the grid
Unit -
Display area Currency / Charge rate/kWh
Factory setting (depending on the country setting)
CO
2
Factor setting for CO
2
reduction
Unit kg/kWh, T/kWh
Setting range 00.01 - 99.99
Factory setting 0.59 kg/kWh
YIELD
Setting
- an OFFSET value for the total energy display
- a measurement compensation factor for the day, year and total energy
display
Unit -
Setting range OFFSET / CALI.
Factory setting -
OFFSET Value parameter for the output energy that is being added to
the current output energy (e.g. transfer value for replacing the
inverter)
Range: 5 digits + unit prefix (k..., M...)
CALI. Correction value parameter to allow the display on the inverter
to match the display of the electricity meter
Range: -5.0 - +5.0% in 0.1 increments