Other resistive loads such as infrared heaters, towel dryers, etc. can also be controlled.
IMPORTANT! In hard water areas, calcication of the heating element may occur, par-
ticularly if the target temperatures are set to over 60 °C. We recommend a yearly inspec-
tion. To execute this, dismantle the heating element from the storage tank and remove
the limescale. Do not scratch the surface of the heating element (formation of corrosion).
Power range
0 - 3 kW
3 - 6 kW
6 - 9 kW
Phase 1
0 - 3 kW contin-
uously variable
Phase 2
-
3 kW xed
3 kW xed
Phase 3
-
-
3 kW xed
WARNING! No electronic thermostats may be used in the loads. The use of
electronic thermostats will lead to destruction of the Ohmpilot and/or the load.
Mechanical temperature switches must be used.
WARNING! Only purely resistive loads may be connected. Connecting an
incorrect load (e.g. fan heater) will lead to destruction of the load.
0 - 3 kW contin-
uously variable
0 - 3 kW contin-
uously variable