installed, an external source (e.g. gas-red heating) must ensure the minimum tempera-
ture.
As an alternative, the Ohmpilot can also ensure the minimum temperature. This may
result in electricity being sourced from the grid.
The maximum temperature must be set on the heating element thermostat. If heating
element 1 (10) does not have a thermostat, the Ohmpilot can also carry out this task as
an alternative (see "Optional settings" section). However, it is imperative that heating
element 2 (12) has a thermostat.
NOTE! At no point can both heating elements be heated simultaneously.
1. The section "Establishing the Data Connection" describes how you can access the
Ohmpilot website.
2. Under HEATER 2, select "3-phase" as the load and the power of the load.