Fronius Primo 5.0-1 SC
Weight 21.6 kg
Permitted ambient temperature -40 °C – +55 °C
Permissible humidity 0 - 100%
EMC emission class B
DC / AC overvoltage category 2/3
Inverter topology Non-insulated transformerless
Voltage classification
Decisive Voltage Classification
(DVC rating)
AC DVC-C
DC DVC-C
Data DVC-A
Protection devices
DC isolation measurement
Warning/shutdown
2)
at R
ISO
< 1 MOHM
Manifestation of DC overload Operating point shift, power limiter
DC disconnector Integrated
Active anti-islanding method Frequency conversion method
Fronius Primo
dummy
Nominal grid voltage 1 ~ NPE 230 V
Mains voltage tolerance
+10 / -5 %
1)
Nominal frequency
50 - 60 Hz
1)
Protection class IP 65
Dimensions h x w x d 645 x 431 x 204 mm
Weight 16.75 kg
Explanation of
footnotes
1) The values quoted are default values; the inverter is configured specific-
ally to meet the needs of the country in question.
2) Depending on the country setup or device-specific settings
(ind. = inductive; cap. = capacitive)
3) Maximum current from a defective PV module to all other PV modules.
From the inverter itself to the PV side of the inverter, it is 0 A.
4) Guaranteed by the electrical configuration of the inverter
5) Current peak when switching on the inverter
Integrated DC