5-26
H95 specifies the DC braking response mode as follows:
If H95 is
set to:
Braking mode Meaning
0
Slow response
The DC braking current gradually ramps up. (The torque
may not be sufficient at the start of DC braking.)
1
Quick response
The DC braking current quickly ramps up. (Depending on
the inertia of the moving loads or the coupling state, the
revolution may be unstable.)
For three-phase 200 V and single-phase 200 V/100 V class series in-
verters
The braking level setting for the three-phase 200 V and single-phase
200 V/100 V class series should be calculated from the DC braking level
I
DB (A) based on the reference current Iref (A), as shown below.
100
(A)
(A)
=(%)Setting
ref
DB
×
I
I
(Example) Setting the braking level IDB at 4.2 Amp (A) for 0.75 kW stan-
dard motors
84100
(A)5.0
(A)4.2
=(%)Setting =×
Nominal applied
motor (kW)
0.1 0.2 0.4 0.75 1.5 2.2 3.7
Reference
current Iref (A)
0.8 1.5 3.0 5.0 8.0 11.0 17.0
The brake function of the inverter does not provide mechanical holding means.
Injuries could occur.