2-21
2.3.8 Switching of SINK/SOURCE (jumper switch)
Before changing the jumper switch, wait for at least five minutes after the power has been turned
off, then check that the DC link bus voltage between the terminals P (+) and N (-) does not ex-
ceed the safety voltage (+25 VDC) using a multimeter.
An electric shock may result if this warning is not heeded as there may be some residual
electric charge in the DC link bus capacitor even after the power has been turned off.
Figure 2.19 Switching of SINK/SOURCE (Jumper Switch)
To switch the sink/source of the digital
input signal, change the position of the
jumper switch using a pair of long-nose
pliers, as shown in Figure 2.19.
At the factory setting, the jumper switch
is positioned at SOURCE for the EU
version except three-phase 200
V
model and at SINK for the Asian and
Japanese versions.
2.3.9 Installing an RS-485 communications card (option)
Figure 2.20 Installing an RS-485 Communications Card
(Option)
When an optional RS-485 Communica-
tions Card is to be used, install it before
putting back the control circuit TB cover.
Align the card with the latch on the in-
verter and attach the card to the con-
nector that is located above terminals
[30A], [30B] and [30C].