Simultaneous + keying may also make the motor ready for jogging de-
pending upon whether keypad operation or terminal command operation is selected
and whether the JOG command is on or off, as listed below.
When operated from keypad (F02 = 0, 2, or 3)
If JOG is:
+
keys
The motor becomes
ready for:
ON Disabled.
Jogging
Normal running
OFF
Toggles between normal and jogging.
Jogging
When terminal command operation is selected (F02 = 1), simultaneous +
keying is disabled.
Select frequency command 2/1--Hz2/Hz1
(Function code data = 11)
Turning the digital input signal Hz2/Hz1 on/off may switch the frequency command
means between frequency command 1 (defined by function code F01) and fre-
quency command 2 (defined by function code C30).
Turning the Hz2/Hz1 command on allows the frequency command 2 to be selected.
Enable data change with keypad--WE-KP
(Function code data = 19)
Turning off the WE-KP command prohibits changing of function code data from the
keypad.
Only when the WE-KP command is on, you may access function code data from the
keypad according to the setting of function code F00 as listed below.
If WE-KP
is set to:
Function code
F00 data
Function
0
Permit editing of function code data
ON
1
Inhibit editing of function code data except F00
OFF Disabled
Inhibit editing of function code data
If the WE-KP command is not assigned to any terminal, the inverter will interpret
WE-KP as being always on.
Cancel PID control--Hz/PID
(Function code data = 20)
Turning the Hz/PID command on/off enables or disables the PID control.
If the PID control is disabled with the Hz/PID being off, the inverter runs the motor
with the frequency manually set by any of multistep, keypad, or analog input.
Refer to the FRENIC-Mini User's Manual (MEH446), Chapter 4, Section 4.8
"PID Frequency Command Generator" for details.