5-41
E39
E50
Coefficient for Constant Feeding Rate Time
Coefficient for Speed Indication
This function code sets a coefficient to be used for setting the constant rate of
feeding time, load shaft speed or line speed and for displaying its output status.
(E39) TimeRate Feeding Const. for Coeff.Freq.
(E50)Indication Speed for Coeff.
=(min) TimeRate Feeding Const.
×
Load Shaft Speed (r/min) = (E50: Coeff. for Speed Indication) × Frequency (Hz)
Line Speed (m/min) = (E50: Coeff. for Speed Indication) × Frequency (Hz)
Where, Freq. is the reference frequency if each expression is for one of the set data
for the constant rate of feeding time, load shaft speed, or line speed; it is the output
frequency if each expression is for the output status monitor.
PID display coefficients A and B (E40 and E41) are the exclusive con-
version factors to equate an indicated value with the process command
and feedback amount in PID control.
E52 Keypad (Menu display mode)
Allows you to select the display mode on the keypad. For details of the operation of
the remote keypad, refer to "Limiting menus to be displayed" in Chapter 3.
This feature is provided to simplify the operation of the keypad. By default E52 is set
at 0 (Menu #1: Data setting) at factory shipment. With this setting (E52 = 0), you
cannot move to another menu with the
or key.
Setting of Function Code E52 Menu items you can choose:
0: Function code data editing mode Menu #1: Data setting
1: Function code data check mode Menu #2: Data checking
2: Full menu mode Menu #1 - #6 (#7*)
* Available only when a remote keypad is set up for operation.
If the full-menu mode is selected, pressing the or key will cycle
through the menu. With the
key, you can select the desired menu
item. Once the entire menu has been cycled through, the display will
return to the first menu item.