3-20
Basic key operation
Before checking the running status on the drive monitor, set function code E52 to "2" (full-menu
mode).
(1) When the inverter is powered on, it automatically enters Running mode. In Running mode,
press the
key to enter Programming mode. The menu for function selection will be dis-
played.
(2) With the menu displayed, use the
and keys to select "Drive monitoring" (
#ope
).
(3) Press the
key to display the desired code in the monitoring item list (e.g.
3_00
).
(4) Use the
and keys to select the desired monitoring item, then press the key.
The running status information for the selected item will appear.
(5) Press the
key to return to the monitoring item list. Press the key again to return to the
menu.
Table 3.11 Drive Monitoring Display Items
LED
monitor
shows:
Contents Unit Description
3_00
Output
frequency
Hz Output frequency before slip compensation
3_01
Output
frequency
Hz Output frequency after slip compensation
3_02
Output
current
A Output current
3_03
Output
voltage
V Output voltage
3_05
Reference
frequency
Hz Reference frequency
3_06
Running
direction
N/A
Displays the running direction currently being outputted.
F: forward; R: reverse, – – – –: stop
3_07
Running
status
N/A
Displays the running status in hex. format. Refer to "
Displaying
running status" on the next page.
3_09
Load shaft
speed
(line speed)
r/min
(m/min)
The unit for load shaft speed is r/min and that for line speed is
m/min.
Display value = (Output frequency Hz before slip compensation)
× (Function code E50)
appears for 10000 (r/min or m/min) or more. When
appears, decrease function code E52 data so that the LED
monitor displays 9999 or below, referring to the above equation.
3_10
PID process
command
N/A
The command is displayed through the use of function code E40
and E41 data (PID display coefficients A and B).
Display value = (PID process command) × (Coefficient A - B) + B
If PID control is disabled, "– – – –" appears.
3_11
PID feedback
amount
N/A
This value is displayed through the use of function code E40
data and function code E41 data (PID display coefficients A and
B).
Display value = (PID feedback amount) × (Coefficient A - B) + B
If PID control is disabled, "– – – –" appears.