2-2
Section 2 System Conguration
2-1-1 Expansion specications
The table below shows the connectable expansion units.
Classication Product name Type Specication
Expansion right side
unit
DIO expansion unit
(with power supply)
NA0E24R-34
Input 14 points, Ry output 10 points, DC power supply
NA0E24T-31 Input 14 points, Tr sink output 10 points, AC power supply
DIO expansion unit
(without power supply)
NA0E08R-3 Input 4 points, Ry output 4 points
NA0E08T-3
Input 4 points, Tr sink output 4 points
NA0E08X-3 Input 8 points
NA0E08T-0
Tr sink output 8 points
NA0E16R-0
Ry output 16 points
NA0E16T-0 Tr sink output 16 points
AIO expansion unit
(without power supply)
NA0AX06-MR Analog input 6 channels
NA0AY02-MR Analog output 2 channels
NA0AW06-MR Analog input 4 channels, Analog output 2 channels
NA0AX02-TC Thermocouple input 2 channels
NA0AX06-TC Thermocouple input 6 channels
NA0AX16-TC Thermocouple input 16 channels
NA0AX06-PT Resistance thermometer element input 6 channels
NA0F-LC1 Load cell unit, 1 channel
Expansion power supply
unit
NA0S-2 Input 100 to 240V AC
NA0S-4 Input 24V DC
Healthy unit
(Terminating connector)
NA8P-HE
Unit for detecting a dropout/fault of expansion right side
units (Note 1)
Expansion left side
unit
Communication unit
NA0LA-RS2 RS-232c: 2 ports (Note 2)
NA0LA-RS5 RS-485: 2 ports (Note 2)
NA0LA-ET1 Ethernet 1 channel (Note 2)
Function unit NA0FA-LC1 High-precision load cell unit, 1 channel (Note 2)
Front board
AIO board
NA3AY02-MR Analog output 2 channels
NA3AW03-MR Analog input 2 channels, Analog output 1 channel
Communication board
NA3LA-RS1 RS-232C: 1 port, RS-485: 1 port (Note 2)
NA3LA-ET1 Ethernet 1 channel (Note 2)
Notes:
1) A healthy unit is used to detect a dropout of expansion right side units.
Be sure to mount a healthy unit to stop the SPF system with a fatal fault when an expansion right side unit is dropped.
Unless a healthy unit is mounted, a dropout of the expansion right side unit is not detected and the SPF system continues
operation in the state where the expansion right side unit is dropped.
Connect a healthy unit to the expansion connector (OUT) of the rightmost expansion right side unit after removing the
cover.
When mounting a healthy unit, register it in the system denition.
A healthy unit is excluded from the number of connectable expansion right side units (Max. 6).
2) A dropout of the communication unit/board and high-precision load cell unit is not detected.